Individual packaging:
1
With a barcode for retail sale
Bulk packaginig: 4
| Operating range | max. 3,8 m³/h |
| Lifting height | max. 7,5 m |
| Media | water, glycol 50% |
| Application | Clear liquid, free of solids, fibrous or mineral oily substances, non-viscous, chemically neutral, non-corrosive and non-explosive, with Similar to water, pumping a fluid with a viscosity pumping a fluid with a viscosity significantly higher than that of water will result in a significant deterioration pump may not function properly, The pump can be operated with glycol up to 50% concentration, in The pump may be operated with up to 50% glycol, in such cases the pump will operate with a reduced capacity. |
| Liquid temperature | +2°C – +110°C for water |
| -30°C – +110°C for a 50% glycol solution | |
| Ambient temperature | 0°C – +70°C for water; RH <95% |
| -30°C – +70°C for a 50% glycol solution; RH <95% | |
| Maximum pressure | 10 bar |
| Minimal inlet pressure depending on the liquid temperature |
0,05 bar up to 75°C |
| 0,5 bar up to 90°C | |
| 1,08 bar up to 110°C | |
| Protection class | IP44 |
| Insulation class | H |
| Energy Efficiency Index | ≤0.20 |
| Installation | with the shaft in a horizontal position |
| Operating modes | AUTO |
| HS – constant speed curves | |
| BL – proportional pressure curves | |
| HD – constant pressure curves | |
| PWM – external input signal control (pulse width modulation) | |
| Voltage | ~230 V (-6% – +10%), 50/60 Hz |
| Power consumption | 5 – 25 W; 0,04 – 0,25 A |
| Connection spacing | 180 mm |
| Connection | G1 1/2 |
| Included | flat gaskets (2 pcs.), 100 cm power cable |